4.4 Description of the units
4 Function description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
4-22
Communication sequence:
1
– The PSENvip starts communication.
Activate = 0/1 pulse edge
– Tool class PLC -> PSENvip Bit 1/2: Bits can have any status
2
– The safety system is ready for communication.
PLC Ready = 0/1 pulse edge
– Tool class PLC -> PSENvip Bit 1/2 = 0 to step 5
3
The PSENvip sends the detected tool class to the safety system.
4
The PSENvip confirms the validity of the tool class registered on the
safety system in step 3.
Acknowledge PSENvip -> PLC = 0/1 pulse edge
5
– The safety system reflects the tool class transmitted by the PSEN-
vip.
– Tool class PLC -> PSENvip Bit 1/2 = 0 or 1, depending on the tool
class
Tool class
123
Tool class PSENvip -> PLC Bit 1 0 1 1
Tool class PSENvip -> PLC Bit 2 1 0 1
PLC Ready
1
0
1
0
1
0
1
0
1
0
Activate
Acknowledge PSENvip -> PLC
1
0
Tool class PSENvip -> PLC Bit 1
1
0
Tool class PSENvip -> PLC Bit 2
Tool class PLC -> PSENvip Bit 1
Tool class PLC -> PSENvip Bit 2
12345 6 7
max. 600 ms
max.
200 ms
max.
200 ms
max.
200 ms