PROFIBUS-DP-Slave Operating Manual 6-3
Standard Function Blocks
ERR (hex) Key Cause/Remedy
00FD DP_SL_ERR_CHK_CFG Configuration data on Master and Slave
do not match; check the configuration
data on the Slave and the Master. See
“Copying the Slave configuration from the
Master configuration”, page 6-4
00FE DP_SL_ERR_BUS_FAULT No communication between Master and
Slave, e.g. incorrect slave ID-number
on the Master, Bus interrupted during
data exchange, Master switched off;
Establish cause and rectify
00FF DP_SL_ERR_FATAL Hardware error; change PSS(1) DP-S
module or PSS SB 3006 DP-S
2000 DP_SL_NO_ERROR No error detected
2001 DP_SL_ERR_SLAVE_NOT_ Slave does not respond or is busy;
READY Reset the module
2002 DP_SL_ERR_DIAG_DATA_ PSS not enabling the DPR or DPR
AREA_NOT_READY is defective; Change PSS(1) DP-S module
or PSS 3006 DP-S.
2003 DP_SL_ERR_ IN_DATA_ PSS not enabling the DPR or DPR
AREA_NOT_READY is defective; Change PSS(1) DP-S module
or PSS 3006 DP-S.
2004 DP_SL_ERR_ OUT_DATA_ PSS not enabling the DPR or DPR
AREA_NOT_READY is defective; Change PSS(1) DP-S module
or PSS 3006 DP-S.
2005 DP_SL_RESET_MODE A reset has been triggered.
2006 DP_SL_ERR_ILLEGAL_MODE Invalid mode has been set
2007 DP_SL_ERR_ILLEGAL_ Undefined slave condition; reset or restart
SLAVE_STATE the module.
INFORMATION
Standard function blocks SB 231 and SB 232 must also be transmitted to
the controller in addition to SB 230. However, parameters do not need to
be set for them, nor do they need to be called up.
NOTICE
The flag range MW 059.00 ... MW 063.16 is reserved for temporary flags.
This range may not be used for global parameters, nor for SB input or
output parameters, otherwise the flags used in the SB will be overwritten.