PROFIBUS-DP-Slave Operating Manual 6-1
Standard Function Blocks
SB 230
Function
• Communication between the PSS and PROFIBUS-DP-Slave
• Trigger a Slave reset
• Trigger static diagnostics
Block Header
SB230
DP-SLAVE
W- BASE ERR -W
B- DB
B- MODE
W: Word, B: Byte
Parameters
• Input parameters
- BASE: Module's start address (Offset)
The module occupies 1024 words after the start address.
These words may not be accessed.
- MODE: = 01: Static diagnostics
= 02: Reset:
All other values: Data exchange (Data_exchange):
- DB: Data block
• Output parameters
ERR: Error message (see table below)
ERR (hex) Key Cause/Remedy
0001 DP_SL_ERR_DPS2_LENGTH Total length calculated for diagnostic,
parameter, input and output data is too
high; reduce the data length!
0002 DP_SL_ERR_DPS2_INIT Hardware initialisation error;
Change PSS(1) DP-S module or
PSS SB 3006 DP-S