Standard Function Blocks
6-2 PROFIBUS-DP-Slave Operating Manual
ERR (hex) Key Cause/Remedy
0003 DP_SL_ERR_SSA_IND Master attempting to change slave
address; reconfigure Master
0004 DP_SL_ERR_DIAG_LEN Diagnostic data length is incorrect;
Change data length
0005 DP_SL_ERR_CFG_LEN Configuration data length is incorrect;
Change length
0006 DP_SL_ERR_PRM_LEN Parameter data length is incorrect;
Change length
0007 DP_SL_ERR_IO_LEN Data length is incorrect (inputs or outputs);
Change length
0008 DP_SL_ERR_DP_WD_TIMEOUT Master monitoring has elapsed;
0009 DP_SL_ERR_WRONG_ADRESS Invalid station address has been set;
Set a valid address (0 - 126) on the switch
and in the data block
000A DP_SL_ERR_IDENT_NR_P Incorrect ID-number in data block;
Correct ID-number: 2500 hex.
000B DP_SL_ERR_WRONG_DB_NR Invalid DB number; select a valid DB
000C DP_SL_ERR_IO_NULL_PTR Input and output data length equal zero;
check the configuration data
1000 DP_SL_ERR_SLAVE_NOT_ Slave does not respond or is busy;
READY Reset the module
1001 DP_SL_ERR_WRONG_SLAVE_ Undefined slave condition; reset or
STATE restart module
1002 DP_SL_ERR_DIAG_DATA_ Access to DPR denied; reset or restart
AREA_NOT_READY module
1003 DP_SL_ERR_CFG_DATA_ Access to DPR denied; reset or restart
AREA_NOT_READY module
00FA DP_SL_ERR_DPRAM_TIMEOUT PSS not enabling the DPR or DPR
is defective; reset or restart module
00FB DP_SL_ERR_SET_PRM Parameter data on Master and Slave do
not match; check the configuration data
00FC DP_SL_ERR_MASTER_NOT_ Master not available, bus interrupted
READY when starting the slave