Pilz ST SB DP S, SW paket PROFIBUS-DP Manual de usuario Pagina 27

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 43
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 26
PROFIBUS-DP-Slave Operating Manual 4-15
Setting Parameters
Example 3:
2 words input and 1 word output,
Special configuration byte: C0,
Length byte input: C1
Length byte output: C0
Diagnostics: 3 words of internal diagnostic data
1 word of device-related diagnostic data
Data word Contents Description
DW 0000 - DW0001 ... Input data
DW 0128 ... Output data
DW 0258 KH 2500 ID-Number
DW 0259 KH 0002 Device-related diagnostics
DW 0384 KH C1C0 Configuration data
DW 0385 KH 00C0
DW 0783 KF 10 max_diag_len [Byte]
DW 0795 KH F5 Pre-assigned
DW 0800 KF 1 Slave address [0-126]
DW 0801 KF 0 Transmission sequence
DW 0810 KF 2 Length of input data in words
DW 0811 KF 1 Length of output data in words
DW 0812 KF 4 Length of diagnostic data in words
DW 0813 KF 3 Amount of configuration data in bytes
DW 0814 KF 0 Pre-assigned
DW 0815 KF 0 Pre-assigned
Vista de pagina 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 42 43

Comentarios a estos manuales

Sin comentarios