Pilz PSS67 F 16DI SB-T Manual de usuario Pagina 47

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 51
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 46
10-1Operating Manual: PSS67 F 16DI SB-T
Technical Details
Electrical data
Supply voltage 24 VDC
Voltage tolerance -15 %/+20 %
Residual ripple DC 5%
Current consumption 90 mA plus load currents taken from the
test pulse outputs
Galvanic isolation Yes, between inputs and
SafetyBUS p
Connection B-coded M12 connector
SafetyBUS p
Transmission rate Max. 500 kBit/s
Cable runs Max. 3500 m
Transmission type Differential two-wire cable
Connection A-coded M12 connector
Digital inputs
Number of inputs 16
Type according to 61101-2 24 VDC Type 1
Separation of supply Yes, between inputs and SafetyBUS p
“1” Signal +15 ... +30 VDC
“0” Signal -3 ... +5 VDC
Input current Typ. 3.5 mA
Input delay < 1 ms
Pulse suppression < 300 µs
Status indicator Green LED
Dedicated test pulses
Number 4 (configurable in pairs as test pulse or
24 VDC output)
Output current at “1” signal Max. 0.125 A per pin
Total load capacity Max. 0.25 A per test pulse group
Cable runs Between test pulse output and input
Max. 100 m