9-5Operating Manual: PSS67 F 16DI SB-T
Recommissioning
NOTICE
When recommissioning, errors may occur when plugging in the connectors
as there is no protection against them being inserted incorrectly. Always
carry out a function test when recommissioning to ensure you exclude the
possibility of such an error.
Faults
If the module is defective or there is a wiring error, all the outputs in the
affected I/O-Group are shut down and the I/O-Group switches to a STOP
condition. An error telegram is then triggered on SafetyBUS p and the error
is entered in the error buffer of the PSS67 F 16DI SB-T.
An error message appears on the display of the controlling PSS. The error
stack display in the programming device can be used to locate the error
(see “SafetyBUS p System Description”).
Module configuration
The procedure for configuring SafetyBUS p and the module PSS67 F 16DI
SB-T is described in the online help of the PSS WIN-PRO system software.
“Load Supply” LED
Reserved for output devices