Pilz PSS67 F 16DI SB-T Manual de usuario Pagina 35

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 51
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 34
Operating Manual: PSS67 F 16DI SB-T 7-9
Example: Single-channel, failsafe input device, with test pulse
Features:
• Depending on the application area and its respective regulations, this
connection diagram is suitable for applications up to Category 2 in
accordance with EN 954-1.
The input device must be approved for failsafe applications.
Please read the instructions provided with the input device.
Short circuits between the cable from the test pulse to the input device
and the cable from the input device to the input will not be detected.
Only input devices with N/C contacts can be tested.