25
Mechanicaldata 751134 751184
Dimensions
Height 100,0mm 100,0mm
Width 22,5mm 22,5mm
Depth
120,0mm 120,0mm
Weight
215g 190g
Thestandardscurrenton200912apply.
Safetycharacteristicdata
Operating
mode
ENISO
138491:
2008
PL
ENISO
138491:
2008
Category
ENIEC
62061
SILCL
ENIEC
62061
PFH
D
[1/h]
IEC61511
SIL
IEC61511
PFD
ENISO
138491:
2008
T
M
[year]
Safetycon
tacts,in
stantaneous PLe Cat.4 SILCL3 2,31E09 SIL3 2,03E06 20
Alltheunitsusedwithinasafetyfunctionmustbeconsideredwhencalculatingthesafety
characteristicdata.
INFORMATION
Asafetyfunction'sSIL/PLvaluesarenotidenticaltotheSIL/PLvaluesof
theunitsthatareusedandmaybedifferent.Werecommendthatyouuse
thePAScalsoftwaretooltocalculatethesafetyfunction'sSIL/PLvalues.
CAUTION!
Itisessentialtoconsidertherelay'sservicelifegraphs.Therelayoutputs'
safetyrelatedcharacteristicdataisonlyvalidifthevaluesintheservicelife
graphsaremet.
ThePFHvaluedependsontheswitchingfrequencyandtheloadontherelayoutput.Ifthe
servicelifegraphsarenotaccessible,thestatedPFHvaluecanbeusedirrespectiveofthe
switchingfrequencyandtheload,asthePFHvaluealreadyconsiderstherelay'sB10d
valueaswellasthefailureratesoftheothercomponents.