PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0510 Fault Diagnostics: Internal error, unit defective} Remedy: Switch supply voltage off and then on a
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0511Power, In1, In2, Out, Reset, Fault Diagnostics: The operating mode selector switch "mode" i
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0512Technical detailsGeneral 750124 750154 751124 751154Approvals CCC, CE, GOST, TÜV, cULus ListedCCC, CE
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0513Electrical data 750124 750154 751124 751154Voltage atInput circuit DC 24,0 V 24,0 V 24,0 V 24,0 VRese
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0514Relay outputs 750124 750154 751124 751154Utilisation categoryIn accordance with the standardEN 60947-
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0515Conventional ther-mal current while loading several contacts750124 750154 751124 751154Ith per contac
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0516Times 750124 750154 751124 751154Delay-on de-energi-sationWith E-STOP typ. 10 ms 10 ms 10 ms 10 msWit
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0517Environmental data 750124 750154 751124 751154Airgap creepageIn accordance with the standardEN 60947-
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0518Mechanical data 750124 750154 751124 751154Spring-loaded termi-nals: Terminal points per connection–
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-0519Order referenceOrder reference Product type Features TerminalsOrder no.PNOZ s4.1 24 VDC Screw
PrefaceThis document is the original document.All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal
...Sachnummer Printed in Germany © Pilz GmbH & Co. KG, 2011+49 711 [email protected] GmbH & Co. KGFelix-Wankel-Straße 27
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-053Safety relay PNOZ s4.1The safety relay provides a safety-related interruption of a safety circuit.The
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-054Safety featuresThe relay meets the following safety requirements:} The circuit is redundant with buil
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-055} Manual start: Unit is active once the input circuit is closed and then the start circuit is closed.
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-056} Calculation of the max. cable length lmax in the input circuit: Rlmax = max. o
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-057Connection} Supply voltageSupply voltage AC DC} Input circuitInput circuit Single-c
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-058} Reset circuit/feedback loopReset circuit/feedback loop Reset circuit Feedback loopAutomatic reset
PNOZ s4.1Operating Manual PNOZ s4.1 21890-EN-059OperationThe unit is ready for operation when the Power LED is permanently lit.LEDs indicate the statu