10
Fault
Diagnostics: Internal error, unit defective
} Remedy: Switch supply voltage off and then on again, change unit if neces-
sary.
Power
Diagnostics: Supply voltage too low
} Remedy: Check the supply voltage.
In1, In2 alternately
Fault
Diagnostics: Short detected between S12 and S22
} Remedy: Rectify short across contacts, switch supply voltage off and then
on again.
In1
Fault
Diagnostics: Power-up blocked due to short-term interruption at S12; input cir-
cuits not operated simultaneously
} Remedy: Open both input circuits, S12 and S22, simultaneously and then
close again.
In2
Fault
Diagnostics: Power-up blocked due to short-term interruption at S22; input cir-
cuits not operated simultaneously
} Remedy: Open both input circuits, S12 and S22, simultaneously and then
close again.
Reset
Fault
Diagnostics: Position of rotary switch is not permitted or rotary switch was ad-
justed during operation.
} Remedy: Switch supply voltage off and then on again.