7-3
7.2 Display elements
7 Operation
Remedy: Correct the hardware registry.
2. Error: A module is missing. Possible cause:
The module has been removed.
The module has an error and is no longer registering after a reset.
The module has an error and switches to a system stop.
The module no longer has a voltage supply.
Remedy: Rectify the above points.
7.2.2 Display elements for DeviceNET diagnostics
Display elements for DeviceNET diagnostics7-][BA_Anzeige DN
The module has LEDs to display various DeviceNet states (“MNS” LED
and “I/O” LED).
Die “MNS” LED indicates the status of the DeviceNet interface and the
network status:
LED for DeviceNet diagnostics Key
MNS Colour Status
- - - No bus connection because
- there is no voltage or
- DUP-MAC-ID test is not com-
plete.
Green “Operational and Online, Con-
nected” status
“Operational and Online, Not Con-
nected” status
Red Recoverable fault (“Minor Fault” or
“Connection Time-out”)
Non-recoverable fault (“Critical
Fault” or “Critical Link Fault”)
Red/
green
Communication error: Error due to
bus access (“Identity Communi-
cation Faulted Request”)
DeviceNet