4-3
4.2 DeviceNET
4 Function description
4.2.3 Selector switch for setting the station address
Selector switch for setting the station address4-][Funktionsbeschreibung_BA_Zusatz DN Station
The station address of a PSSu is set via the “ADDRESS” DIP switches
(“1”, “2”, “4” “8” “16” and “32”). The DIP switches are binary coded. Per-
mitted station addresses are in the range 0
D
... 63
D
.
A station address is set via a combination of the relevant binary coded
switches:
“ADDRESS” DIP switch Key Example
Switch designation OFF ON Station address 52
D
- - Not connected
S2 Transmission rate
S1
32 0 32
D
16 0 16
D
808
D
404
D
202
D
101
D
INFORMATION
The station address should only be set when the module is
switched off (no voltage applied).
The settings are only transferred when booting. Any changes
made to the settings during operation will not be transferred.
Each station address on DeviceNet must be unique.
ADDRESS
OFF
ON
S2
S1
32
16
8
4
2
1
- -
BAUD