Installation
}
TheunitshouldbeinstalledinacontrolcabinetwithaprotectiontypeofatleastIP54.
}
UsethenotchontherearoftheunittoattachittoaDINrail.
}
EnsuretheunitismountedsecurelyonaverticalDINrail(35mm)byusingafixingele
ment(e.g.retainingbracketoranendangle).
Wiring
Pleasenote:
}
Informationgiveninthe"Technicaldetails"mustbefollowed.
}
Outputs1314,2324,3334aresafetycontacts;output4142isanauxiliarycontact
(e.g.fordisplay).
}
Auxiliarycontact4142shouldnotbeusedforsafetycircuits!
}
Topreventcontactwelding,afuseshouldbeconnectedbeforetheoutputcontacts(see
technicaldetails).
}
Calculationofthemax.cablerunsl
max
intheinputcircuit:
R
lmax
=max.overallcableresistance(seeTechnicaldetails)
R
l
/km=cableresistance/km
}
Usecopperwirewithatemperaturestabilityof60/75°C.
}
Sufficientfuseprotectionmustbeprovidedonalloutputcontactswithcapacitiveandin
ductiveloads.
}
Whenconnectingmagneticallyoperated,reedproximityswitches,ensurethatthemax.
peakinrushcurrent(ontheinputcircuit)doesnotoverloadtheproximityswitch.
}
Thepowersupplymustcomplywiththeregulationsforextralowvoltageswithprotect
iveelectricalseparation(SELV,PELV)inaccordancewithVDE0100,Part410.
Importantfordetectionofshortsacrosscontacts:
Asthisfunctionfordetectingshortsacrosscontactsisnotfailsafe,itistestedbyPilzduring
thefinalcontrolcheck.Ifthereisadangerofexceedingthecableruns,werecommendthe
followingtestaftertheinstallationofthedevice:
1. Unitreadyforoperation(outputcontactsclosed)
2. ShortcircuitthetestterminalsS12,S22fordetectingshortsacrosstheinputs.
3. Theunit'sfusemustbetriggeredandtheoutputcontactsmustopen.Cablelengthsin
thescaleofthemaximumlengthcandelaythefusetriggeringforupto2minutes.
4. Resetthefuse:removetheshortcircuitandswitchoffthesupplyvoltageforapprox.1
minute.