PNOZc1
OperatingManualPNOZc1
22197EN02
11
Relayoutputs 710001
Utilisationcategory
Inaccordancewiththestandard EN6094751
Auxiliarycontacts,AC15at 230V
Max.current 5,0A
Auxiliarycontacts,DC13(6cycles/min)at 24V
Max.current 5,0A
Safetycontacts,AC15at 230V
Max.current 5,0A
Safetycontacts,DC13(6cycles/min)at 24V
Max.current 5,0A
UtilisationcategoryinaccordancewithUL
Voltage 240VACG.U.(samepolarity)
Withcurrent 6,0A
Voltage 24VDCG.U.
Withcurrent 6,0A
Contactfuseprotection,externalsafetycontacts
Inaccordancewiththestandard EN6094751
Blowoutfuse,slow 6A
Circuitbreaker,24VAC/DC,characteristicB/C 6A
Contactfuseprotection,externalauxiliarycontacts
Blowoutfuse,slow 6A
Circuitbreaker,24VAC/DC,characteristicB/C 6A
Contactmaterial AgCuNi+0,2µmAu
Conventionalthermalcurrentwhileloadingsev
eralcontacts
710001
IthpercontactatUBDC
Conv.therm.currentwith1contact 6,00A
Conv.therm.currentwith2contacts 6,00A
Conv.therm.currentwith3contacts 5,00A
Times 710001
Switchondelay
Withautomaticresettyp. 250ms
Withautomaticresetmax. 450ms
Withautomaticresetafterpowerontyp. 250ms
Withautomaticresetafterpoweronmax. 450ms
Withmanualresettyp. 125ms
Withmanualresetmax. 450ms
Delayondeenergisation
WithESTOPtyp. 15ms
WithESTOPmax. 30ms
Withpowerfailuretyp. 60ms
Withpowerfailuremax. 100ms
Recoverytimeatmax.switchingfrequency1/s
AfterESTOP 300ms
Afterpowerfailure 300ms