Electricaldata 710001
Max.inrushcurrentimpulse
Currentpulse,A1 1,80A
Pulseduration,A1 4,0000ms
Currentpulse,inputcircuit 0,35A
Pulseduration,inputcircuit 25,0ms
Currentpulse,feedbackloop 0,15A
Pulseduration,feedbackloop 2,0ms
Currentpulse,startcircuit 0,15A
Pulseduration,startcircuit 2,0ms
Max.overallcableresistanceRlmax
Dualchannelwithdetectionofshortsacrosscon
tactsatUBDC
15Ohm
Min.inputresistanceatpoweron 88Ohm
Voltageat
InputcircuitDC 24,0V
ResetcircuitDC 24,0V
FeedbackloopDC 24,0V
Currentat
InputcircuitDC 30,0mA
ResetcircuitDC 40,0mA
Feedbackloop 40,0mA
Numberofoutputcontacts
Instantaneoussafetycontacts(N/O) 3
Auxiliarycontacts(N/C) 1
Inputs 710001
Number 2
Relayoutputs 710001
Max.shortcircuitcurrentIK 1kA
Utilisationcategory
Inaccordancewiththestandard EN6094741
Auxiliarycontacts,AC1at 240V
Min.current 0,01A
Max.current 6,0A
Max.power 1500VA
Auxiliarycontacts,DC1at 24V
Min.current 0,01A
Max.current 6,0A
Max.power 150W
Safetycontacts,AC1at 240V
Max.current 6,0A
Min.current 0,01A
Max.power 1500VA
Safetycontacts,DC1at 24V
Max.current 6,0A
Min.current 0,01A
Max.power 150W