Pilz PSSu XB F -T Manual de usuario Pagina 25

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 33
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 24
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-3
6.2 Terminal configuration
6 Wiring
6.2Terminal configuration6200Terminal configuration6-][Klemmenbelegung XB
Base module Terminal configuration
Screw terminals:
PSSu BP 2/16S
PSSu BP 2/16S-T
Cage clamp terminals:
PSSu BP 2/16C
PSSu BP 2/16C-T
Without C-rail:
11-21: 0 V periphery supply
(11-21 linked internally)
12-22: 0 V periphery supply
(12-22 linked within the base module)
13-23: +24 V periphery supply
(13-23 linked within the base module)
14-24: +24 V periphery supply
(14-24 linked internally)
31-41-32-42-33-43-34-44 not con-
nected
Screw terminals:
PSSu BP-C 2/16S
PSSu BP-C 2/16S-T
Cage clamp terminals:
PSSu BP-C 2/16C
PSSu BP-C 2/16C-T
With C-rail:
11-21: 0 V periphery supply
(11-21 linked internally)
12-22: 0 V periphery supply
(12-22 linked within the base module)
13-23-33-43: C-rail supply
(13-23-33-43 linked within the base
module)
14-24: +24 V periphery supply
(14-24 linked internally)
31-41-32-42-34-44 not connected
2111
2212
2313
2414
4131
4232
4333
4434
2111
2212
2313
2414
4131
4232
4333
4434
Vista de pagina 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 31 32 33

Comentarios a estos manuales

Sin comentarios