9.1 Technical details
9 Technical details
99000Technical detailsTechnical details9-9.1Technical details9100Technical details9-][Technische Daten_PDP_DI
Technical details
Application range Standard/Failsafe
Electrical data
Internal supply voltage Supply
Supply voltage U
B
DC 24 V
Voltage tolerance -30 %/+25 %
Power consumption at U
B
1.2 W
Inputs
Number 8
Input voltage 24 V DC
Input current 3.0 mA
Potential isolation between input and internal bus voltage yes
Outputs (configurable as semiconductor outputs or
test pulse outputs)
Infeed for Load Supply
Voltage 24 V DC
Voltage tolerance -30 %/+25 %
Max. continuous current that the external power supply
must provide
4.0 A
Max. unit fuse protection F1 4 A
Max. unit fuse protection F1 in according with UL508 4 A
Number of positive-switching single-pole semiconductor
outputs
8
Short circuit-proof yes
Potential isolation between semiconductor output and in-
ternal bus voltage
yes
Potential isolation between semiconductor output and in-
put
no
Typ. output current at “1” signal and rated voltage of sem-
iconductor output
0.50 A
Permitted current range 0.00 - 0.60 A
Residual current at “0” signal 0.02 mA
Permitted loads inductive, capacitive, resistive
Max. internal voltage drop 200 mV
Terminal voltage when switching off inductive loads -45 V
Number of test pulse outputs 8
Number of outputs that can be configured as test pulses 8
Max. output current at “1” signal 0.50 A
Short circuit-proof yes
Max. cable runs between test pulse output and input 20 m
Hardware processing times
Max. processing time for input when signal changes from
“1” to “0”
1.000 ms
Max. processing time for input when signal changes from
“0” to “1”
1.200 ms
Min. processing time for input when signal changes from
“1” to “0”
0.50 ms
Min. processing time for input when signal changes from
“0” to “1”
0.70 ms