6 Supply Voltage
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-2
Use a 5-pin M12 plug-in connector to connect the module to the exter-
nal supply voltage.
The module also has an M12 socket which is physically adjacent to the
M12 connector; this is used to distribute the supply voltage to other
modules.
Anschluss_Weiterl_Zeichnung PDP
Fig. 6-1: Example for connecting and distributing the supply voltage
Anschluss_Weiterl_Warnung PDP
Anschluss_Weiterl_Funktionserde PDP
Pinbelegung PDP
WARNING!
The current load capacity of the M12 plug-in connector is 4 A
per connector. You must ensure that this value is not exceeded.
Exceeding the permitted current load capacity can damage the
plug-in connector. Please note that the connection of the addi-
tional supply voltage is not monitored for overload.
INFORMATION
We recommend that you connect the functional earth to the
upper fixing screw.