5.1 General installation guidelines
5 Installation
55000InstallationInstallation5-5.1General installation guidelines5100General installation guidelines5-Montage_multi_mini_allgemein
The unit should be installed in a control cabinet with a protection type
of at least IP54.
Fit the safety system to a horizontal mounting rail. The venting slots
must face upwards and downwards. Other mounting positions could
destroy the safety system.
Use the notch on the rear of the unit to attach it to a mounting rail.
In environments exposed to heavy vibration, the unit should be
secured using a fixing element (e.g. retaining bracket or end angle).
Push the unit upwards or downwards before lifting it from the
mounting rail.
To comply with EMC requirements, the mounting rail must have a low
impedance connection to the control cabinet housing.
Montage_multi_mini_Temperatur
The ambient temperature of the PNOZmulti units in the control
cabinet must not exceed the figure stated in the technical details,
otherwise air conditioning will be required.
Montage_EMV ESD
5.1.1 Dimensions
Dimensions5-Abmessungen PNOZ mml2p
CAUTION!
Damage due to electrostatic discharge!
Electrostatic discharge can damage components. Ensure
against discharge before touching the product, e.g. by touching
an earthed, conductive surface or by wearing an earthed
armband.
120 (4.72")
* 100 (3,94")
98 (3.86")
22,5
(0.88")