Pagina 1 - PSS-Range

The spirit of safety.Programmable Safety SystemsPSS-RangePSS Standard Function Blocks MBS Emergency Stop CircuitsVersion 2.2Operating ManualItem No. 1

Pagina 2

1-2IntroductionModular Block System: Emergency Stop CircuitsMBS Modular Block SystemSafety-related areas can be equipped with a multitude of safety de

Pagina 3 - Contents

8-16ExamplesModular Block System: Emergency Stop CircuitsSB 067RFK_K4B - SSNRX - RFK1X - RFK2X - RSetX - EinFG - XK- XKB 010E 0.00 .RFK-K-G1 -E 0.00 .

Pagina 4

8-17Modular Block System: Emergency Stop Circuits Notes

Pagina 5

8-18ExamplesModular Block System: Emergency Stop CircuitsFig 8-14: Wiring diagramE-STOP monitoring with monitoring of feedback loop, category 4Blocks

Pagina 6

8-19Modular Block System: Emergency Stop CircuitsKB 011 -M 110.01 .RLO-1 -E 0.01 .E-STOP -E 0.02 .E-STOP -M 110.00 .RLO-0 -M 110.01 .RLO-1 -- M 80.02S

Pagina 7 - Appendix 9-1

8-20ExamplesModular Block System: Emergency Stop Circuits Notes

Pagina 8

9-1Modular Block System: Emergency Stop CircuitsAppendixAssignment table: category and requirement classIn process engineering, safety requirements mu

Pagina 9

9-2AppendixModular Block System: Emergency Stop CircuitsStandard function blocks: current versionsINFORMATIONThis manual is intended exclusively for u

Pagina 10 - Introduction

9-3Modular Block System: Emergency Stop CircuitsChanges to the standard function blocksINFORMATIONWhen imported into existing projects, new parameters

Pagina 11

9-4AppendixModular Block System: Emergency Stop CircuitsSB062: Emergency stop monitoringVersion Date CRC1.0 21.09.99 7F641.1 29.09.99 ADE91.2 31.05.00

Pagina 12

9-5Modular Block System: Emergency Stop CircuitsSB063: Emergency stop monitoringVersion Date CRC1.0 03.07.02 1AB5SB065: Feedback loop monitoring (RFK)

Pagina 13 - Definition of symbols

1-3Modular Block System: Emergency Stop CircuitsCategories / requirement classesEN 954-1 divides safety devices into categories.All standard function

Pagina 14

9-6AppendixModular Block System: Emergency Stop Circuits• Input parameters RVen, SPSV, RPSV, WBan, WBim introduced.Changes from Version 1.1 to Version

Pagina 16

AUS B L BR D TR DK E F FIN GB I SE IRL ... www PRC ROK A J MEX NZ P NL USA CHIn many countries we arerepresented by sales partners.Please refer

Pagina 17 - Safety guidelines

1-4IntroductionModular Block System: Emergency Stop CircuitsOverview of manual1 IntroductionThe chapter you are reading provides an introduction to th

Pagina 18

1-5Modular Block System: Emergency Stop CircuitsDefinition of symbolsInformation in this manual that is of particular importance can be identifiedas f

Pagina 19

1-6IntroductionModular Block System: Emergency Stop CircuitsTerminology• The term “input” is frequently abbreviated to “I” (e.g. I-Parameter).• The te

Pagina 20 - Fault detection

2-1Modular Block System: Emergency Stop CircuitsSoftware packageThe “MBS Emergency Stop Circuits” software package is part of the PilzMBS Modular Bloc

Pagina 21 - Fault detection techniques

2-2OverviewModular Block System: Emergency Stop Circuits• SB063 E-STOPMonitoring E-STOP button up to category 4 in accordance withEN 954-1, 03/97 and

Pagina 22

3-1Modular Block System: Emergency Stop CircuitsSafety guidelinesThese safety guidelines are an important part of this manual. Failure tokeep to thes

Pagina 23 - Intended Use

3-2SafetyModular Block System: Emergency Stop CircuitsApplication guidelines• The instructions given in the “Safety Manual” and in the “InstallationMa

Pagina 24

3-3Modular Block System: Emergency Stop CircuitsStandardsTo use the SBs correctly you will need to have a good knowledge of therelevant standards and

Pagina 25

All rights to this manual are reserved by the publishers. Copies may be made forinternal purposes.While every effort has been made to ensure that the

Pagina 26

3-4SafetyModular Block System: Emergency Stop CircuitsFault detectionThe detection of errors and defects is an important function of the PSS, inadditi

Pagina 27

3-5Modular Block System: Emergency Stop CircuitsFault detection techniquesVarious options are available to the user to help detect and rectify errors

Pagina 28

3-6SafetyModular Block System: Emergency Stop CircuitsPulsed input signalsInput devices for inputs with infrequent operation (e.g. E-STOP, offbuttons,

Pagina 29 - MBS Basics

4-1Modular Block System: Emergency Stop CircuitsThe software package “MBS Emergency Stop Circuits” is designed for usewithin the failsafe section of t

Pagina 30

4-2Intended UseModular Block System: Emergency Stop CircuitsIntended use of the standard function blocksSB060: Emergency stop monitoringSB060 is a sta

Pagina 31

4-3Modular Block System: Emergency Stop CircuitsSB062: Emergency stop monitoringSB062 is a standard function block for monitoring E-STOP buttons up to

Pagina 32

4-4Intended UseModular Block System: Emergency Stop Circuits• With or without automatic reset when E-STOP is released• With or without prompt for func

Pagina 33

4-5Modular Block System: Emergency Stop Circuits• If wiring is to be laid outside the control cabinet, feedback loops must usetest pulses.• Feedback l

Pagina 34

4-6Intended UseModular Block System: Emergency Stop CircuitsSB070: Initialisation of administration data block (DB015)SB070 is used to calculate the g

Pagina 35 - Input parameter SSNR

5-1Modular Block System: Emergency Stop CircuitsBlock designStructureSafety-related areas can be equipped with a multitude of safety devicessuch as (e

Pagina 36

1Modular Block System: Emergency Stop CircuitsIntroduction 1-1MBS Modular Block System 1-2Categories / requirement classes 1-3Overview of manual 1-4De

Pagina 37 - Fault diagnostics

5-2MBS BasicsModular Block System: Emergency Stop CircuitsFormal parameters and actual parametersParameters can be set on the MBS standard function bl

Pagina 38

5-3Modular Block System: Emergency Stop CircuitsAdministration data blocks DB015, DB016 and DB017Data blocks DB015, DB016 and DB017 are permanently sp

Pagina 39 - Output parameter FG/ENBL

5-4MBS BasicsModular Block System: Emergency Stop CircuitsDB017DB016DW0000DB015Block 1200 data wordsBlock 2200 data wordsBlock 3200 data wordsBlock 42

Pagina 40

5-5Modular Block System: Emergency Stop CircuitsBlocks contained in the administration data blocksEach standard function block occupies 1 data word pe

Pagina 41 - Global parameters

5-6MBS BasicsModular Block System: Emergency Stop CircuitsDW0000 (DB015)If parameters for a standard function block’s input parameterSSNR are not with

Pagina 42

5-7Modular Block System: Emergency Stop CircuitsInput parameter SSNRMBS standard function blocks have input and output parameters whichcan be adapted

Pagina 43 - Standard Function Blocks

5-8MBS BasicsModular Block System: Emergency Stop CircuitsNOTICE• One MBS standard function block must be used for each safety device.• Each standard

Pagina 44

5-9Modular Block System: Emergency Stop CircuitsFault diagnosticsError typesOn programmable safety systems from the PSS-range, a distinction ismade be

Pagina 45 - Feedback loop monitoring

5-10MBS BasicsModular Block System: Emergency Stop CircuitsFault diagnostics using the administration data blocksData words DW0001 ... DW0200 of an ad

Pagina 46

5-11Modular Block System: Emergency Stop CircuitsTemporary flag range in MBS blocksInternally, MBS blocks use the flags in the range M 64.00 ... M69.3

Pagina 47

2ContentsModular Block System: Emergency Stop CircuitsSB063: Emergency stop monitoring 4-3SB065: Feedback loop monitoring 4-4SB067: Feedback loop moni

Pagina 48

5-12MBS BasicsModular Block System: Emergency Stop CircuitsAssignment of input and output parametersInput and output parameters should be assigned in

Pagina 49

5-13Modular Block System: Emergency Stop CircuitsGlobal parametersBlock 6 (DW1001 ... DW1023) of the administration data blocks containsglobal paramet

Pagina 50

5-14MBS BasicsModular Block System: Emergency Stop CircuitsDW1014 ReservedDW1015 Counter for monitoring the SSNRDW1016 ReservedDW1017 ReservedDW1018 R

Pagina 51

6-1Modular Block System: Emergency Stop CircuitsStandard Function BlocksGuidelines for selecting standard function blocksSeveral standard function blo

Pagina 52

6-2Standard Function BlocksModular Block System: Emergency Stop CircuitsSB062 E-STOPSB062 is used in applications up to category 4. This standard func

Pagina 53

6-3Modular Block System: Emergency Stop CircuitsFeedback loop monitoringSB067 RFK_K4SB067 is used in applications up to category 4. This standard func

Pagina 54

6-4Standard Function BlocksModular Block System: Emergency Stop CircuitsInitialisation of administration data blocksSB070 INIT_MBSSB070 exclusively in

Pagina 55

6-5Modular Block System: Emergency Stop CircuitsNotes

Pagina 56

6-6Modular Block System: Emergency Stop CircuitsStandard Function BlocksSB060: Emergency stop monitoring, category 2Block headerInput parameters•SSNR:

Pagina 57

Modular Block System: Emergency Stop Circuits 6-7Output parameters•FG: Enable flag bitFG = 0: Not enabledFG = 1: Function enabled when no errors are p

Pagina 58

3Modular Block System: Emergency Stop CircuitsInitialisation of administration data blocks 6-4SB070 INIT_MBS 6-4SB071 INIT_MBS 6-4SB060: Emergency sto

Pagina 59

6-8Modular Block System: Emergency Stop CircuitsStandard Function BlocksGlobal parameters used in administration data block DB 015Global parameters ma

Pagina 60

Modular Block System: Emergency Stop Circuits 6-9 Notes

Pagina 61

6-10Modular Block System: Emergency Stop CircuitsStandard Function BlocksSB061: Emergency stop monitoring, category 4Block headerInput parameters•SSNR

Pagina 62

Modular Block System: Emergency Stop Circuits 6-11QAut= 1: Automatic reset whenEIN= 1: E-STOP-button is releasedQAnf= 0:INFORMATIONAutomatic reset is

Pagina 63

6-12Modular Block System: Emergency Stop CircuitsStandard Function Blocks- Bit 03: With: “Automatic reset (PSS cold start)”:E-STOP button operated and

Pagina 64

Modular Block System: Emergency Stop Circuits 6-13- E 002: Parameter errorSSNR assigned more than once ORDW1015 in DB015 was not incrementedGlobal par

Pagina 65

6-14Modular Block System: Emergency Stop CircuitsStandard Function BlocksSB062: Emergency stop monitoring, category 4Block headerInput parameters•SSS

Pagina 66

Modular Block System: Emergency Stop Circuits 6-15AuSt = RLO-1 (M 110.01): No initial reset required.Sequence: When the PSS is powered up or cold star

Pagina 67

6-16Modular Block System: Emergency Stop CircuitsStandard Function BlocksError messagesAny fault that is detected will be stored in the corresponding

Pagina 68

Modular Block System: Emergency Stop Circuits 6-17• Error messages on the CPU-display- NoneGlobal parameters used in administration data block DB015Th

Pagina 69

4ContentsModular Block System: Emergency Stop CircuitsOutput parameters 6-23Functions 6-24Error messages 6-25Global parameters used in the administrat

Pagina 70

6-18 Modular Block System: Emergency Stop CircuitsStandard Function BlocksSB063SB063: Emergency stop monitoring, category 4Block headerInput parameter

Pagina 71

Modular Block System: Emergency Stop Circuits 6-19AuSt = 1: No initial reset requiredSequence: When the PSS is cold/warm started or the I/O-Group is s

Pagina 72

6-20 Modular Block System: Emergency Stop CircuitsStandard Function BlocksSequence of function test:• Press E-STOP button• Release E-STOP button• Pres

Pagina 73

Modular Block System: Emergency Stop Circuits 6-21- Bit 08: Synchronisation error N/C contact 2Remedy: Check button, cable and input card, release the

Pagina 74

6-22 Modular Block System: Emergency Stop CircuitsStandard Function BlocksSB065SB065: Feedback loop monitoringBlock headerInput parameters•SSNR: Safet

Pagina 75

Modular Block System: Emergency Stop Circuits 6-23•TFbL: Time for feedback loop monitoring when switching on/offPermitted value range in ms: 0 ... 200

Pagina 76

6-24 Modular Block System: Emergency Stop CircuitsStandard Function BlocksWiring for category 4If you use two contactors in applications for category

Pagina 77

Modular Block System: Emergency Stop Circuits 6-25The acknowledgements FbL1 and FbL2 are also monitored in the staticcondition. If there are discrepan

Pagina 78

6-26 Modular Block System: Emergency Stop CircuitsStandard Function Blocks- Bit 03: Fault as the signal changes at input parameter ON,feedback loop 2

Pagina 79

Modular Block System: Emergency Stop Circuits 6-27Global parameters used in the administration data blocksGlobal parameters may be set in OB120 using

Pagina 80

5Modular Block System: Emergency Stop CircuitsEmergency stop monitoringwith manual start (start-up and operation), category 4 8-6Emergency stop monito

Pagina 81 - Link Blocks

6-28Modular Block System: Emergency Stop CircuitsStandard Function BlocksSB067SB067: Feedback loop monitoringBlock headerInput parameters•SSNR: Safety

Pagina 82

Modular Block System: Emergency Stop Circuits 6-29Error messagesAny fault that is detected will be stored in the corresponding error dataword (SSNR) o

Pagina 83

6-30Modular Block System: Emergency Stop CircuitsStandard Function Blocks- Bit 06: Faults which occur as the pulse edge changes at the inputparameter

Pagina 84

Modular Block System: Emergency Stop Circuits 6-31 Notes

Pagina 85

6-32Modular Block System: Emergency Stop CircuitsStandard Function BlocksSB070SB070: Initialisation of administration data block (DB015)Block headerIn

Pagina 86

Modular Block System: Emergency Stop Circuits 6-33Table for setting the global parameters:INFORMATION• All times must be entered in ms.• The values su

Pagina 87

6-34Modular Block System: Emergency Stop CircuitsStandard Function BlocksSB070Please note:Entering excessively high time values for monitoring operati

Pagina 88

Modular Block System: Emergency Stop Circuits 6-35 Notes

Pagina 89

6-36Modular Block System: Emergency Stop CircuitsStandard Function Blocks SB071SB071: Initialisation of administration data blocksBlock headerInput pa

Pagina 90

Modular Block System: Emergency Stop Circuits 6-37Table for setting the global parameters:INFORMATION• All times must be entered in ms.• The values su

Pagina 92

6-38Modular Block System: Emergency Stop CircuitsStandard Function Blocks SB071Please note:Entering excessively high time values for monitoring operat

Pagina 93 - Fig. 8-8: Timing diagram

7-1Modular Block System: Emergency Stop CircuitsCheck list• Safety regulations- Which safety regulations need to be met?- Aid: Relevant standards and

Pagina 94

7-2Link BlocksModular Block System: Emergency Stop CircuitsThese can be optimised during commissioning.- Enter a minimum scan time.- If test pulses ar

Pagina 95 - Fig. 8-10: Timing diagram

7-3Modular Block System: Emergency Stop Circuits• Create OB101- Reset all enable flags (FG/ENBL) at the start of the OB or at the start ofthe cycle.

Pagina 96

7-4Link BlocksModular Block System: Emergency Stop Circuits Notes

Pagina 97 - Fig. 8-12: Timing diagram

8-1Modular Block System: Emergency Stop CircuitsApplications and parameters of individual blocksThe following examples are designed to show the applic

Pagina 98

8-2ExamplesModular Block System: Emergency Stop CircuitsFig. 8-1: Wiring diagramEmergency stop monitoring with manual start (start-up and operation),c

Pagina 99

8-3Modular Block System: Emergency Stop CircuitsProgram:Insert the following additional commands at the end of OB101:: A DB015: I DW1015: BEKB 002 -E

Pagina 100 - Examples

8-4ExamplesModular Block System: Emergency Stop CircuitsEmergency stop monitoring with automatic start (start-up andoperation), category 2Block used:

Pagina 101

8-5Modular Block System: Emergency Stop CircuitsProgram:Insert the following additional commands at the end of OB101:: A DB015: I DW1015: BEKB 002 -M

Pagina 102

1-1Modular Block System: Emergency Stop CircuitsThis manual describes how to manage the standard function blocks in the“MBS Emergency Stop Circuits” s

Pagina 103 - Fig. 8-15: Timing diagram

8-6ExamplesModular Block System: Emergency Stop CircuitsEmergency stop monitoring with manual start (start-up and operation),category 4Block used: SB0

Pagina 104

8-7Modular Block System: Emergency Stop CircuitsProgram:Fig. 8-6: Timing diagramInsert the following additional commands:: L M80.00 .NA_1: U M80.01 .N

Pagina 105 - Appendix

8-8ExamplesModular Block System: Emergency Stop CircuitsEmergency stop monitoring with automatic start-up, manual start(operation) and function test,

Pagina 106

8-9Modular Block System: Emergency Stop CircuitsFig. 8-8: Timing diagramKF 000005 -M 116.01 .SBUS_Grp_01E 40.01 .E-STOP1 -E 40.02 .E-STOP1 -M 110.01 .

Pagina 107

8-10ExamplesModular Block System: Emergency Stop CircuitsFeedback loop monitoring (shutdown with two contactors connected inseries), category 4Block u

Pagina 108

8-11Modular Block System: Emergency Stop CircuitsFig. 8-10: Timing diagramA1.0010E0.0210E0.3110M72.0110PSS-START10E0.0110E0.0810A1.0810SB065FBLW - SSN

Pagina 109

8-12ExamplesModular Block System: Emergency Stop CircuitsFig 8-11: Wiring diagramFeedback loop monitoring (shutdown with two main contactorsconnected

Pagina 110

8-13Modular Block System: Emergency Stop CircuitsSB 067RFK_K4B - SSNRX - RFK1X - RFK2X - RSetX - EinFG - XK- XKB 006E 0.01 .RFK-K-M1.1 -E 0.02 .RFK-K-

Pagina 111

8-14ExamplesModular Block System: Emergency Stop CircuitsFeedback loop monitoring (selective shutdown), category 4Block used: SB067/RFK_K4WARNING!If o

Pagina 112

8-15Modular Block System: Emergency Stop CircuitsProgram:Motor 1.1 :Segment 01: L A 1.16 .K-G1 K-M1.1 switches on if K-G1 is “1” and: U E 0.08 .M1.1_S