Wiring
OperatingManualPSSuEFAII(T)(R)
21981EN05
22
– Checkthatthecableisfirmlyseated.
}
Basemodulewithcageclampterminals:
– Insertthescrewdriver[4]intothesquarehole[1].
– Insertthestrippedcableintotheroundfixinghole[2],asfarasitwillgo[5].
– Pulloutthescrewdriver[6].
– Checkthatthecableisfirmlyseated.
Pleasenote:
}
Theminimumcablecrosssectionforfieldconnectionterminalsonthebasemodulesis
0.14mm
2
(AWG26).
}
Themaximumcablecrosssectionforfieldconnectionterminalsis:
– Digitalinputs:1.5mm
2
(AWG16)
– Digitaloutputs:2.0mm
2
(AWG14)
– Inputs/outputsonthecountermodules:1.5mm
2
(AWG16)
– Analogueinputs/outputs:1.5mm
2
(AWG16)
– Communicationcables:1.5mm
2
(AWG16)
– Testpulseoutputs:1.5mm
2
(AWG16)
– Powersupply:2.5mm
2
(AWG12)
– Functionalearth:2.5mm
2
(AWG12)
Comentarios a estos manuales