Pilz PNOZ s11 C 24VDC 8 n/o 1 n/c Manual de usuario Pagina 9

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 13
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 8
PNOZ s11
Operating Manual PNOZ s11
21693-EN-08
9
Relay outputs 750111 751111
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Auxiliary contacts, AC15 at 230 V 230 V
Max. current 5,0 A 5,0 A
Auxiliary contacts, DC13 (6 cy-
cles/min) at
24 V 24 V
Max. current 5,0 A 5,0 A
Safety contacts, AC15 at 230 V 230 V
Max. current 5,0 A 5,0 A
Safety contacts, DC13 (6 cycles/
min) at
24 V 24 V
Max. current 5,0 A 5,0 A
Contact fuse protection, external
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Circuit breaker, 24V AC/DC,
characteristic B/C
6 A 6 A
Contact fuse protection, external
auxiliary contacts
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Circuit breaker, 24 V AC/DC,
characteristic B/C
6 A 6 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au
Conventional thermal current
while loading several contacts
750111 751111
Ith per contact at UB DC
Conv. therm. current with 1 con-
tact
6,00 A 6,00 A
Conv. therm. current with 2 con-
tacts
6,00 A 6,00 A
Conv. therm. current with 3 con-
tacts
6,00 A 6,00 A
Conv. therm. current with 4 con-
tacts
6,00 A 6,00 A
Conv. therm. current with 5 con-
tacts
6,00 A 6,00 A
Conv. therm. current with 6 con-
tacts
5,70 A 5,70 A
Conv. therm. current with 7 con-
tacts
5,30 A 5,30 A
Conv. therm. current with 8 con-
tacts
5,00 A 5,00 A
Vista de pagina 8
1 2 3 4 5 6 7 8 9 10 11 12 13

Comentarios a estos manuales

Sin comentarios