
Commissioning
Operating Manual PNOZ mc7p
1003050-EN-01
12
Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator. It is possible to
define which inputs and outputs on the safety system will communicate with CC-Link.
Please note:
} Information given in the "Technical details" must be followed.
} Use copper wire that can withstand 75 °C.
Please note the following when connecting to CC-Link :
} The following minimum requirements of the connection cable and connector must be
met:
– Only use standard industrial Ethernet cable and connectors.
– Only use double-shielded twisted pair cable and shielded RJ45 connectors (indus-
trial connectors).
– 100BaseTX cable in accordance with the Ethernet standard (min. Category 5)
} Measures to protect against interference:
Ensure the requirements for the industrial use of CC-Link are met, as stated in the In-
stallation Manual published by the User Group.
ATTENTION!
Only connect and disconnect the expansion module when the supply volt-
age is switched off.
Interface assignment
It is possible to define which outputs on the safety system will communicate with CC-Link.
The connection to CC-Link is made via a 5-pin screw connector.
1: DA (Channel A)
2: DB (Channel B)
3: DG (Earth)
4: SLD (Cable shield)
5: FG/PE (Functional earth)
6
6.1
6.2
Comentarios a estos manuales