2.3 Configuration in the PNOZmulti Configurator
2Muting
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
2-4
2.3Configuration in the P NOZmulti Configurator2300Configuration in the P NOZmulti Configurator2-
2.3.1 Functions
Functions2-Muting_Konfiguration_Funktionen
Muting via light beam devices or limit switches
Override option in case of fault
Max. muting time can be set
Muting sensors can be monitored for simultaneity
Configuration of bounce time for contact-based muting sensors
Sequence of the muting sensors can be monitored
Operating modes
Sequential muting
Parallel muting
–Cross muting
2.3.2 Input parameters
Input parameters2-Muting_Konfiguration_Eingangsparameter
Muting sensor 1
N/O contact of muting sensor 1
Muting sensor 1 = 0: Not operated
Muting sensor 1 = 1: Operated
Muting sensor 2
N/O contact of muting sensor 2
Muting sensor 2 = 0: Not operated
Muting sensor 2 = 1: Operated
Light curtain
Light curtain = 0: Interrupted
Light curtain = 1: Not interrupted
Assign the light curtain input parameter to the output of the light cur-
tain function element. The light curtain function element must be
configured with an automatic reset.
Muting sensor 3
N/O contact of muting sensor 3
Muting sensor 3 = 0: Not operated
Muting sensor 3 = 1: Operated
Muting sensor 4
N/O contact of muting sensor 4
Muting sensor 4 = 0: Not operated
Muting sensor 4 = 1: Operated
Muting override
Muting override = 1: Suspend the muting function if a fault occurs
(override) to override the muting channel.
Reset = 0/1 pulse edge: Reset muting after an error or start the muting
time.