6.3 Seriesconnectionof4decentralisedmodules
Youcanconnectupto4decentralisedmodulesinseriestoaPNOZmultilinkmodule.
6.4 Voltagedrop
Themax.cablelengthdependsonthevoltagedropinthesupplyvoltagecables.Thelevel
ofvoltagedropisdeterminedbythe:
}
Cableresistanceonthesupplyvoltagecables
}
Operatingcurrentofthemodules
}
Loadonthemodules
Toincreasethemax.cablelength,theinputvoltagecanbepermanentlyincreasedbythe
voltagetolerance(seeTechnicalDetails).
6.4.1 Guidelinesforvariouscabletypes
Cabletype Voltagedropper10mandper100mA
PSSSBBUSCABLELC 0.1V
Sensorcable0.25mm
2
0.15V
Sensorcable0.34mm
2
0.11V
Sensorcable0.5mm
2
0.07V